On-Grid (Grid-Tied) System Design

The simplest and cheapest PV system: no batteries. Solar powers your home first, surplus is exported, and the grid fills any gap — day or night.

Lesson 1

How it works

The grid-tie inverter synchronises with the grid's voltage and frequency, pushing solar current into your distribution board. Your loads draw from solar first; the net meter records whatever flows in or out.

☀ PV ArrayDC, 300–600 V DC Isolator+ SPD + fuses Grid-Tie InverterMPPT · anti-islanding AC BoardMCB + RCD 🏠 Loads NetMeter ⇄ 🗼 Grid
DC powerAC power (import/export)
Energy flows in both directions through the net meter: export at noon, import at night.

Advantages

  • Lowest cost per kWp — no batteries
  • Fastest payback (often 3–6 years with net metering)
  • Almost no maintenance
  • The grid acts as an unlimited "virtual battery"

Limitations

  • No power during outages — anti-islanding shuts the inverter down
  • Needs utility approval and net-metering agreement
  • Savings depend on export tariffs
  • Export limits may cap system size
Lesson 2

Design procedure, step by step

  1. Find your energy consumption

    Take 12 months of bills and average the units (kWh). Use the annual average for net-metered systems.

    E_daily (kWh/day) = Monthly units (kWh) ÷ 30
  2. Get Peak Sun Hours and losses

    Look up PSH for your city (e.g. NASA POWER, PVGIS, NREL). Apply a Performance Ratio (PR) of 0.75–0.80 to cover temperature, dust, mismatch, cable and inverter losses.

  3. Size the PV array

    PV (kWp) = E_daily ÷ (PSH × PR)
    No. of modules = PV (W) ÷ Module rating (Wp) → round up

    Check roof area: about 5–6 m² per kWp for modern 20%+ efficient modules.

  4. Choose the inverter

    Pick an inverter whose AC rating gives a DC/AC ratio of 1.1–1.3. Slight oversizing of the array increases morning/evening output with minimal clipping.

    Inverter (kW AC) ≈ PV (kWp) ÷ 1.1…1.3
  5. Design the strings

    Modules in series add voltage. The string must stay below the inverter's max DC voltage on the coldest morning and above the MPPT minimum on the hottest afternoon.

    Voc_cold = Voc × [1 + β_Voc × (T_min − 25)] → N_max = ⌊V_max,inv ÷ Voc_cold⌋
    Vmp_hot = Vmp × [1 + β_Vmp × (T_cell,max − 25)] → N_min = ⌈V_MPPT,min ÷ Vmp_hot⌉

    Also check: string Isc × 1.25 ≤ inverter MPPT max input current; parallel strings on one MPPT must be identical.

  6. Size cables and protection

    Voltage drop (%) = (2 × L × I × ρ) ÷ (A × V) × 100 — keep DC ≤ 2%, AC ≤ 3%

    DC side: string fuses (if ≥3 strings in parallel), DC isolator, Type 2 DC SPD. AC side: MCB rated ≥ 1.25 × inverter output current, RCD (Type A/B per inverter), AC SPD, earthing of frames and inverter.

  7. Grid approval & net metering

    Submit single-line diagram, datasheets and inverter certification (e.g. IEC 62109, IEC 61727 / IEEE 1547 / UL 1741) to your utility. Install the bidirectional meter after approval.

Lesson 3

Worked example

A home uses 300 kWh/month, PSH = 5, PR = 0.78, using 550 Wp modules (Voc 49.6 V, Vmp 41.6 V, β_Voc −0.27 %/°C, β_Vmp −0.35 %/°C). Inverter: 3 kW, max 600 V DC, MPPT 120–550 V.

StepCalculationResult
Daily energy300 ÷ 3010 kWh/day
Array size10 ÷ (5 × 0.78)2.56 kWp
Modules2560 ÷ 550 = 4.66 → 5 (we choose 6 for a 1.1 DC/AC ratio)6 × 550 W = 3.3 kWp
Inverter3.3 ÷ 1.13 kW
Voc at 5 °C49.6 × (1 + 0.0027 × 20)52.3 V
Max in series⌊600 ÷ 52.3⌋11
Vmp at 70 °C cell41.6 × (1 − 0.0035 × 45)35.0 V
Min in series⌈120 ÷ 35.0⌉4
String layout1 string of 6 → Voc_cold 314 V, Vmp_hot 210 V ✔1 × 6
Annual yield3.3 × 5 × 0.78 × 365≈ 4,700 kWh
Practice

On-grid sizing calculator

Change any value — results and the full working update instantly.

Load & site

kWh / month
h / day
%

Module

Wp
V
V
%/°C

Temperatures & inverter

°C
°C
V
V

Results

Daily energy
PV array
Modules
Inverter
String length
Roof area
Annual yield
Bill offset
Before you install

On-grid design checklist

Test yourself

On-grid quiz

1. What happens to a standard on-grid system during a power cut?

Grid-tie inverters must disconnect when the grid fails to protect utility workers.

2. A home uses 450 kWh/month with PSH 5 and PR 0.75. Required array?

450 ÷ 30 = 15 kWh/day; 15 ÷ (5 × 0.75) = 4 kWp.

3. Which temperature determines the maximum number of modules in a string?

Voltage rises as temperature falls, so Voc is highest on cold mornings.

4. A typical DC/AC ratio for grid-tied systems is…

Modest oversizing improves inverter utilisation with little clipping loss.

5. Recommended maximum DC cable voltage drop?

Keep DC losses near 1–2% for efficiency.